Coil and duct allowances

This group turns the room loads into a coil duty. The application works in the order the Explain trace shows, and the sections below use the same names, so a reader can follow the page against the trace.

Coil and duct allowances

Every allowance has a tick box; off means the allowance is left out of the calculation. Percentages within the same bracket add together rather than compounding.

From room load to coil duty

  1. Room sensible heat (RSH) and room latent heat (RLH): the room's own loads, increased by the supply-side allowances and by the Design margins.
  2. Effective room sensible heat (ERSH) and effective room latent heat (ERLH): the room loads plus the share of the fresh-air load that bypasses the coil.
  3. Effective sensible heat factor (ESHF): the sensible share of the effective room load. It fixes the slope of the coil line.
  4. Grand total heat (GTH): everything the coil must remove, including the rest of the fresh-air load, increased by the return-side allowances.
  5. Apparatus dew point (ADP): the coil surface temperature that lets one coil carry the effective load at that sensible share.
  6. Dehumidified air quantity: the supply-air flow that carries the effective sensible load at the temperature rise the coil can give.

Bypass factor

On screen: Bypass factor (coil bypass factor).

The share of the air passing through the coil that leaves it untreated, as if it had bypassed the coil. A typical value for a four-row coil is about 0.10; deeper or closer-finned coils have a lower factor.

Setting Value
Default 0.10
Allowed 0.00 to 0.90

It appears at four steps of the chain, where OASH and OALH are the sensible and latent loads of the fresh air:

ERSH = RSH + BF × OASH

ERLH = RLH + BF × OALH

ESHF = ERSH ÷ (ERSH + ERLH)

GTH = ( ERSH + ERLH + (1 − BF) × (OASH + OALH) ) × (1 + return-side allowances ÷ 100)

supply-air rise = (1 − BF) × (Troom − ADP)

Apparatus dew point. The coil is treated as a surface at one temperature, the ADP. Air leaving it is a mixture of air at the ADP and untreated air, in the proportion given by the bypass factor. On a psychrometric chart, the line from the room condition to the ADP on the saturation curve must have the slope given by the ESHF, and the application searches down the saturation curve from the room's dew point for the first temperature that satisfies this. Two things can go wrong, and both are reported as a flag on the room's result and in the Explain trace:

A higher bypass factor moves more of the fresh-air load onto the room side, lowers the supply-air rise, and so increases the air quantity.

Min airflow

On screen: Min airflow (when a room's minimum airflow is more than the coil needs). A room can carry its own Min airflow, in air changes per hour, per unit floor area, or as a straight airflow. When that minimum is more than the Dehumidified air quantity the coil chain calculated, the room's Supply air becomes the minimum and the same ERSH is carried by more air, so the Rise shrinks and the Supply temperature rises. This setting says what the coil does with the extra air; it applies to every room in the run whose minimum wins, and does nothing to a room whose calculated flow is already larger.

Setting Value
Default Bypass the extra air around the coil
Choices Bypass the extra air around the coil · Reheat the supply air

Bypass the extra air around the coil. The coil, its ADP and the Grand total heat stay as calculated; the extra air passes the coil untreated and mixes back in. The Explain trace's Minimum airflow step, present for every room with a minimum, shows the calculated flow and the minimum, and when the minimum wins the new rise and the effective bypass factor the extra air implies.

Reheat the supply air. All the air passes the coil and is warmed back to the supply temperature the room needs. The reheat is sensible only, never below zero, and is added to the Grand total heat:

Qreheat = ρ × cp × Vmin × ( Tsupply − Tleaving )

The trace adds a Reheat step and a Grand total heat with reheat step after the air side. The hour-by-hour peak search still ranks hours on the calculated coil load and applies the minimum at the winning hour.

Either way the room is flagged MIN AIRFLOW, the Explain panel says how the extra air was handled, and the Entering temperature and the OA>SUPPLY check use the enforced flow.

Fixed ADP

Pin the apparatus dew point to a temperature of your choice instead of letting the search above find it — for example the ADP of a coil you have already selected. Off by default; when on, every room in the run uses this one value.

Setting Value
Default Off, 10 °C
Allowed 0 °C up to, but not including, the indoor temperature

The value is entered in the temperature unit of the Units setting and stored in °C. A value that is out of range is only reported while the box is ticked, so a stale number behind an unticked box never blocks Calculate.

What changes. Only the air side. RSH, RLH, ERSH, ERLH, ESHF and the grand total heat do not depend on the ADP and are unchanged. The supply-air rise, the dehumidified air quantity and the supply, entering and leaving temperatures all follow from the fixed value through the same formulas as before, with the fixed ADP in place of the solved one.

What is still checked. The search still runs, to learn the ADP the room would have needed, and the Explain trace shows both figures on the ADP step: Required ADP and ADP. When the fixed value is warmer than the required one, or when the search finds no ADP at all (the reheat and frost cases above), the coil cannot dry the air enough for the room's design humidity, and the room is flagged ADP>REQUIRED. A fixed value colder than required raises no flag. With a fixed ADP the ADP, Rise and air columns are always filled, never blank.

Supply gain

On screen: Supply gain (supply duct heat gain).

Heat picked up by the supply duct between the coil and the room, as a percentage of the room sensible load.

Setting Value
Default Off, 2 %
Allowed 0 to 50 %

It is added to the room sensible load together with supply duct leakage and fan heat:

RSH = room sensible × (1 + (supply duct heat gain + supply duct leakage + fan heat) ÷ 100) × (1 + sensible safety ÷ 100)

Supply leak

On screen: Supply leak (supply duct leakage).

Supply air lost from the duct before it reaches the room, as a percentage. It is the only allowance that applies to both the sensible and the latent room load, because leaked air carries moisture as well as heat.

Setting Value
Default Off, 2 %
Allowed 0 to 50 %

RLH = room latent × (1 + supply duct leakage ÷ 100) × (1 + latent safety ÷ 100)

Fan heat

Heat added to the supply air by the supply fan, as a percentage of the room sensible load. It is applied with the two supply duct allowances above.

Setting Value
Default Off, 5 %
Allowed 0 to 50 %

Return gain

On screen: Return gain (return duct heat gain).

Heat picked up by the return duct on its way back to the coil, as a percentage of the grand total heat.

Setting Value
Default Off, 1 %
Allowed 0 to 50 %

It is applied with return duct leakage:

GTH = ( ERSH + ERLH + (1 − BF) × (OASH + OALH) ) × (1 + (return duct heat gain + return duct leakage) ÷ 100)

Return leak

On screen: Return leak (return duct leakage).

Air lost from the return duct, as a percentage of the grand total heat. Applied with the other return-side allowances above.

Setting Value
Default Off, 1 %
Allowed 0 to 50 %